****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** ________________________________________________________________________________ F3200 V4.02 database at 00/10/42 81:36:01 ________________________________________________________________________________ Database version 0102 Database CRC $3916 Database last changed at 05/07/04 19:29:49 by user 0 [ ] Keypad type = 4428.x/Warning System/External Bell Legacy 1603.4 Bells/BELLS ISOL disabled MAF board enabled AZC modules 1 Relay modules 1 Display boards 0 FF zones = MAF FF RDU remote ack = enabled FF Auto ack = disabled FF display Cause by default = disabled Always flash non-maf alm LEDs = disabled Always send non-maf FF alm to RDU = disabled FF alarm event printing = disabled New cause new alarm = disabled Multiple cause updates = enabled Switch to newest alarm = disabled Show zone number on FF display = enabled Show isolated alarms in FF = enabled Show point text in FF for zone alarm = disabled Brigade test relay activate = enabled Brigade alarm relay country code = disabled ( i.e. steady ) FIP MCP maps to zone 8 All zones isolated = standby operate Event printing = enabled Print relay controls = enabled Printer lines per page 60 Printer Baud rate 9600 Event printing selections : Zone = Yes System = Yes Sys running = Yes Circuit = Yes Point = Yes Relay = Yes Event history selections : Zone = Yes System = Yes Sys running = Yes Circuit = Yes Point = Yes Relay = Yes ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** Daylight saving start : Month = OCT Hour = 2 Minute = 0 Day = last SUN Time difference : Hour = 1 Minute = 0 Daylight saving end : Month = MAR Hour = 3 Minute = 0 Day = last SUN Time difference : Hour = 1 Minute = 0 Fault action text : Contact your service company Mains frequency selected = 50 hz Mains fail = fault after 8 hrs : No Charger high/low = fault : Yes Battery low = fault : Yes Battery connection test enable : Yes Battery hourly test enable : Yes Battery daily 40 min test enable : Yes All RZDUs disabled RZDU protocol type = LCD AutoTest start time 09:00 AutoTest test alarm = disabled AutoTest inhibit dates : 25 DEC , 26 DEC , 1 JAN , 2 JAN plus weekends Alarm buzzer enabled = Y Zone fault buzzer enabled = Y System fault buzzer enabled = Y Non-maf zone fault buzzer enabled = N Fault sounder after 8 hours of fault = N Fault sounder after 8 hours of isolate = N Fault sounder "8 hr" period in 6 minute units = 0 Buzzer operates in loud mode when door open = No Warning system maps to MAF = Y External bell maps to MAF = Y New Zealand mode options (NDU only) : NZ mode enabled = No Display board installed = N Battery very low alarm enabled = N Evac defect fault enabled = N External defect fault enabled = N ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** FF mode door open keys enabled. ------------------------------------- Prev[Y] Next[Y] Ack[Y] Reset[Y] Isolate[Y] Relay[Y] XBel Isol[Y] Warn Sys Isol[Y] AIF Mode[Y] Clear[Y] Recall[Y] Ancil Isol[Y] Zone[Y] System[Y] Numeric[Y] Enter[Y] Batt test[Y] OR[Y] AND[Y] XOR[Y] NOT[Y] Print[Y] Set[Y] Test[Y] Alarm test[Y] Fault test[Y] Brigade test[Y] FF mode door closed keys enabled. ------------------------------------- Prev[N] Next[N] Ack[N] Reset[N] Isolate[N] Relay[N] XBel Isol[N] Warn Sys Isol[N] AIF Mode[N] Clear[N] Recall[N] Ancil Isol[N] Zone[N] System[N] Numeric[N] Enter[N] Batt test[N] OR[N] AND[N] XOR[N] NOT[N] Print[N] Set[N] Test[N] Alarm test[N] Fault test[N] Brigade test[N] Non FF mode door open keys enabled. ------------------------------------- Prev[Y] Next[Y] Ack[Y] Reset[Y] Isolate[Y] Relay[Y] XBel Isol[Y] Warn Sys Isol[Y] AIF Mode[Y] Clear[Y] Recall[Y] Ancil Isol[Y] Zone[Y] System[Y] Numeric[Y] Enter[Y] Batt test[Y] OR[Y] AND[Y] XOR[Y] NOT[Y] Print[Y] Set[Y] Test[Y] Alarm test[Y] Fault test[Y] Brigade test[Y] Non FF mode door closed keys enabled. ------------------------------------- Prev[N] Next[N] Ack[N] Reset[N] Isolate[N] Relay[N] XBel Isol[N] Warn Sys Isol[N] AIF Mode[N] Clear[N] Recall[N] Ancil Isol[N] Zone[N] System[N] Numeric[N] Enter[N] Batt test[N] OR[N] AND[N] XOR[N] NOT[N] Print[N] Set[N] Test[N] Alarm test[N] Fault test[N] Brigade test[N] Remote sounder silence options : sysflt reset = Y FF actions = Y all commands = N Global network sounder silence : Any key Tx=Y Cmd Tx=Y Receive=Y ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** ________________________________________________________________________________ Zone names ________________________________________________________________________________ Zone 01 Detector Circuit 1 Zone 02 Detector Circuit 2 Zone 03 GAS START Zone 04 GAS RELEASED Zone 05 GAS INHIBITED Zone 06 GAS ISOLATED Zone 07 Zone 08 FIP MANUAL CALL POINT ________________________________________________________________________________ ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** ________________________________________________________________________________ Relay names ________________________________________________________________________________ Relay 01 ALERT Relay 02 EVACUATE Relay 03 GAS RELEASE SOLENOID Relay 04 SYSTEM INOPERATIVE Relay 05 Relay 06 Relay 07 Relay 08 ________________________________________________________________________________ ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** ________________________________________________________________________________ Circuit data. AZC Alarm Mode Delay B1 B3 in out Inst alm text type time time text ________________________________________________________________________________ 01 Smoke standard standard inst-alarm normal 0 0 Manual 02 Smoke standard standard inst-alarm normal 0 0 Manual 03 Manual standard standard inst-alarm normal 0 0 Manual 04 PSW standard standard alarm normal 0 0 Manual 05 Manual standard standard inst-alarm normal 0 0 Manual 06 Manual standard standard inst-alarm normal 0 0 Manual 07 Smoke standard standard inst-alarm normal 0 0 Manual 08 Smoke standard standard inst-alarm normal 0 0 Manual ________________________________________________________________________________ ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** ________________________________________________________________________________ Zone data. Zone Latching MAF ANC1 WARNSYS EXTBELL LED ________________________________________________________________________________ 01 Yes Yes No Yes Yes 1 02 Yes Yes No Yes Yes 2 03 Yes Yes No Yes Yes 3 04 Yes Yes No Yes Yes 4 05 No No No No No 5 06 No No No No No 6 07 Yes Yes No Yes Yes 7 08 Yes Yes No Yes Yes 8 ________________________________________________________________________________ ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** ________________________________________________________________________________ Relay data. Relay Supervise Latching MAF Mode/Led Isolatable Test Supervise Act ________________________________________________________________________________ ANC1 No No Yes Load Yes Yes Yes ANC2 No No Yes Load Yes Yes Yes ANC3 No No Yes Yes Yes Yes 01 Yes Yes Yes 9 Yes Yes Yes 02 No No Yes 10 Yes Yes Yes 03 Yes Yes Yes 11 Yes Yes Yes 04 Yes Yes Yes 12 Yes Yes Yes 05 No No Yes 13 Yes Yes Yes 06 No No Yes 14 Yes Yes Yes 07 No No Yes 15 Yes Yes Yes 08 No No Yes 16 Yes Yes Yes ________________________________________________________________________________ ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** ________________________________________________________________________________ Ancillary relay names ________________________________________________________________________________ ANC1 GUARD RELAY ANC2 ANC3 ________________________________________________________________________________ ________________________________________________________________________________ Alarm text names ________________________________________________________________________________ 1 Smoke 2 Heat 3 FSW 4 Manual 5 Valve 6 PSW 7 SPKLR 8 9 ________________________________________________________________________________ ________________________________________________________________________________ Access code assignments ________________________________________________________________________________ User Initials 0 [ ] 1 Not assigned 2 Not assigned 3 Not assigned 4 Not assigned 5 Not assigned 6 Not assigned 7 Not assigned 8 Not assigned 9 Not assigned ________________________________________________________________________________ ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** ________________________________________________________________________________ Output logic equations. ________________________________________________________________________________ Number of free blocks = 497 ,used = 15 MAF relays controlled by output logic are : ANC1 R1=Z1A+Z2A+Z3A+Z4A R2=Z4A+V1 R3=T1 OC1=V1 OC2=Z3A OC3=Z4A OC4=Z5A+Z6A+OC5+Z3:6(1)I+Z1:6(1)F+R1F+R2F+R3F+R4F+R1I+R2I+R3I+R4I OC5=Z1:2(1)I AR1=V1 V1=Z1A.Z2A.^Z5A+Z3A T1[S30:0]=V1 R4=OC4 Default equation for open collector xx is zone xx alarm End of equations ________________________________________________________________________________ ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ****** FF zone configuration ________________________________________________________________________________ SID Zone1 Zone2 MapFF AlmSndr MultiAlm AckTX AckRX LocAck ResetFF IsoFF Global No No No No No No No No End of FF zone configuration data. ________________________________________________________________________________ End of database ________________________________________________________________________________ ****** F3200 V4.02 "F3200 AS4428 1 ZONE GAS CONTROL" ******