Alarm display selection

You can configure how the Alarms are displayed in the Alarm tab.

By default, the Alarm tab displays alarms in zones, meaning that only the first point alarm in any zone is displayed. Subsequent point alarms in the same zone are not displayed separately. This is BASIC ALARM DISPLAY mode. By selecting ENHANCED ALARM DISPLAY, the ALARMS tab displays all alarms in any zone. This means that a zone can appear several times in the alarms list, if it contains several points in alarm.

On the Service tab, you can select which version of alarm display is used. Press the ALARM DISPLAY button to switch between modes. The label on the button shows which version will be selected if you press the button.

Note: Regardless of this setting, the ALM/PRI2 tab always lists every point and every zone in alarm. This tab is not intended for use by brigade personnel, and does not present an AS4428.3 Fire Brigade Panel display.